THERMIC FLUID HEATING SYSTEM

This system is forced circulation fully automatic thermic fluid heater where thermic fluid is circulated in a closed loop through heater and user equipment circuit where the heat is dissipated to process. The same thermic fluid is re-circulated through heater for heating. The thermic fluid heater gives high temperature upto 300 oC using thermic fluid oil at near atmospheric pressure as compared to steam heating which requires 85 Kg/Cm2 pressure. 

The new vertical four pass thermic fluid heater is suitable for Process industries in rapidly changing and undependable energy situations. It gives you an assurance for rated output on  any solid fuel like coal, Lignite, wood, husk, bagasse etc

High Efficiency Multi Fuel Horizontal Thermic Fluid Heater High Efficiency Multi Fuel Vertical Thermic Fluid Heater

Thermic Fluid Heater- Horizontal

Thermic Fluid Heater - vertical

Technical Specification of Horizontal Thermic Fluid Heater

Parameter Unit

Model

FBSH-400 FBSH-600 FBSH-1000 FBSH-1500

FBSH-2000

Heat Output

Kcal/Hr

4,00,000

6,00,000

10,00,000

15,00,000

20,00,000

Max.Fluid Outlet Temperature

oC

300

Max. Head at heater Outlet

M/c

27

Efficiency on GCV With APH+

%

75

Without APH+

%

70

Rated fuel consumption Steam Coal

Kg/hr

118

177

296

444

592

Lignite

Kg/hr

152

228

381

571

762

Agro-waste

Kg/hr

162

242

404

606

808

Thermic Fluid Pump Motor

Kw

9.30

11.00

15.00

22.00

30.00

I.D.Fan Motor

Kw

3.70

5.62

11.25

11.25

15.00

Over fire fan motor

Kw

-

1.50

2.25

3.70

3.70

Total Load

Kw

13.00

18.12

28.50

36.95

48.70

Expansion Tank Capacity

Liters

800

800

1000

1000

1250

Overall Dimensions

Length

mm

4600

6000

7500

7800

10000

With

mm

3800

4000

4500

5400

6200

Height

mm

3000

3100

3400

3800

4200

Technical Specification of Vertical Thermic Fluid Heater

Parameter Unit

Model

FBSV-400 FBSV-600 FBSV-1000 FBSV-1500

FBSV-2000

Heat Output

Kcal/Hr

4,00,000

6,00,000

10,00,000

15,00,000

20,00,000

Max.Fluid Outlet Temperature

oC

300

Max. Head at heater Outlet

M/c

27

Efficiency on GCV Steam Coal

%

76

Agro-waste

%

70

Rated fuel consumption Steam Coal

Kg/hr

116

175

290

435

580

Lignite

Kg/hr

150

226

376

564

752

Agro-waste

Kg/hr

174

260

433

650

866

Thermic Fluid Pump Motor

Kw

7.5

9.3

11.0

18.5

30

I.D.Fan Motor

Kw

3.7

5.5

9.3

11.0

15.0

F.D.Fan Motor Steam Coal

Kw

-

1.5

2.2

3.7

5.5

Agro-waste

Kw

-

2.2

3.7

5.5

7.5

Total Load Steam Coal

Kw

11.2

16.3

22.5

33.2

50.0

Agro-waste

Kw

-

17.0

24.0

35.0

52.5

Expansion Tank Capacity

Liters

800

800

1000

1000

1250


| Home | About Us | Products | Services | ClientsInquiry Form | Opportunities | Site Map | Reach us |